The PUE is the main metric of energy efficiency in a data centre environment:
The minimum value of the PUE is theoretically 1. Ideally we want to reduce the PUE to as low a figure as possible.
The PUE does not take account of how efficient our IT loads are.
Reducing energy costs requires a consistent across-the board approach to reducing both the IT and non-IT power loads, subsection 1.
Best to take advantage of easy wins, avoid diminishing returns.
Depending on business needs, certain workloads may be better served by migrating them to virtual servers provisioned on a cloud environment.
Infrastructure equipment replacement carries high capital costs. Seek:
These calculations would need to consider the characteristics of the equipment in varying conditions: e.g. part-load and seasonal.
See [Rasmussen, 2017] for full details.
There are two key air streams in a data centre:
We want servers to get coldest possible air. Therefore all air should come from the cooling unit. There should be no “leakage” of hot air back to the inlets of servers.
Cooling units work best if they take in the hottest air in the room and cool it down. The greater the differential between the hot return air and the ambient temperature, the better the cooling performance will be. Efficiency seriously hampered if CRACs pull in already cold air.
Containment is possible in both raised-floor and solid-floor environments.
As a minimum, we must be using hot / cold aisle arrangements, regardless of how small our data centre environment is!
A commonly encountered example is the targeted supply from raised floor with flooded return to CRAC as seen in subsection 3.
Economisation aims to reduce the number of hours the refrigeration system must be in operation. There are many ways to do this, with the principal methods detailed in Niemann et al. [2011].
Some common configurations often seen in smaller environments are:
Direct airside economisation is normally found in conjunction with Air-Cooled DX CRACs but can be employed with any cooling system. The idea is simple: when the outdoor air is cold enough, it is blown directly into the data centre.
Key requirements are:
Glycol-cooled DX and Water-cooled DX CRACs can have an additional coil fitted within the case. When the ambient temperature outside is low enough, the compressor can be shut down and a diverter valve sends water from the dry cooler / cooling tower outdoors to the economiser coil.
John Niemann, John Bean, and Victor Avelar. Economizer modes of data center cooling systems. White Paper 132, APC Schneider Electric, 2011. URL https://www.apc.com/whitepaper/?wp=132.
Neil Rasmussen. The different types of air distribution for IT environments. White Paper 55, APC Schneider Electric, 2017. URL https://www.apc.com/whitepaper/?wp=55.