Recommended background reading from the APC white paper library APC white papers:
Heat removal is necessary for all data centre environments, from tiny closets to large multi-acre dedicated facilities. Almost all the electrical power input to IT equipment is converted to heat. Without any means to remove heat, the temperature in the closed space will rise quickly.
Temperature quantifies how hot an environment is.
In Europe, temperature is usually expressed in Celsius (formerly Centigrade) unit. The Fahrenheit scale (°F) is sometimes encountered in US-centric publications about cooling systems.
The most common conversion is to/from Fahrenheit.
The Kelvin scale is rarely encountered in applied cooling work but is directly related to the Celsius scale:
Equipment and humans can only tolerate a certain range of temperatures, or thermal envelope. If IT equipment is operated outside of its thermal envelope it can lead to CPU throttling, thermal shutdown and reduced long-term lifespan.
The American Society of Heating, Refrigeration and Air conditioning Engineers (ASHRAE) have published a number of standards for thermal envelopes of data centre environments. The most recent guidelines published in 2011 are given in section 2.
Classes A1 to A4 represent normal data centre environments, where environmental controls (e.g. cooling) are used. The ASHRAE recommended thermal envelope is between 18 and 27 degrees.
In order to keep the temperature and relative humidity within permitted limits, we must rely on some method of cooling.
subsection 1 shows the available cooling methods for smaller data centres and server rooms. As the IT Load increases in size, we often require dedicated cooling solutions.
Fans can be used on in smaller data centre environments to keep the temperature under control by exchanging the air with the ambient / outside environment, subsection 2.
Fans can be thermostatically controlled. They can be powered from a UPS to ensure the fans run even when mains power fails.
In practical terms, anything more than a simple closet with a few devices will need refrigerated cooling. Conduction, passive ventilation and fan-assisted cooling schemes are ultimately limited by the outdoor temperature. Consider trying to keep a room at 22C when the outdoor temperature is 34C!
The only way to make heat “flow uphill” from cold to hot is to assist it. From our point of view, we want to remove heat from our computer room and reject it to the atmosphere, to keep the room temperature under control. section 3 shows the basic refrigeration cycle. For a more thorough treatment, see Evans [2014].
There are four stages evident in section 3:
Watch the Refrigeration Cycle 101 video on YouTube
There are two main categories of cooling system seen in data centre environments, direct expansion (DX) and chilled water.
Refrigerated cooling is provided in a data centre environments by two main families of equipment: Direct eXpansion (DX) and Chilled Water. DX systems where the evaporator directly meets air in the data centre environment are the simplest to understand and most common in small and medium environments.
DX systems normally take the form of a Computer Room Air Conditioner, or CRAC. A CRAC is normally a large floor-standing unit containing the evaporator coil, blower fan, compressor and other components. For in-depth information refer to Evans [2012].
CRACs are most usually seen in so-called downflow configuration as in section 5.
Other configurations include upflow (reverse of the above, but only on a solid floor), horizontal and other configurations. Cooling units are sometimes located in other areas and ducted to the data centre environment.
For the cooling system to work properly, we must use a hot aisle / cold aisle arrangement. Where a raised floor is used, the perforated tiles must be in the cold aisle, and not in the hot aisle.
CRAC evaporator fans normally run continuously. The refrigeration system cycles on and off under thermostatic control to maintain the selected temperature. Control is often based on the return, supply or space air temperature. More sophisticated control strategies are becoming common, but the basic idea outlined above is sufficient.
Self-contained units have all refrigeration components within the CRAC’s casing. The condenser supply and exhaust are ducted from the outdoors. Limited in cooling capacity to approx 15 kW due to unit size and ducting, subsection 6.
Candidate for up to 15 kW. Often seen in small on-site server rooms.
Direct expansion, often abbreviated DX, cooling systems house the evaporator, compressor and expansion valve within the CRAC unit. The condenser is sited externally, with wiring and refrigerant connections from the CRAC unit, subsection 7.
Candidate for 7 kW to 200 kW. Multiple units often used for larger capacities and to provide redundancy (see later).
An alternative layout of the Air-Cooled DX system has the compressor is located in the outdoor unit, called a condensing unit. This arrangement is commonly called the split system.
The Glycol-cooled DX replaces the air-cooled condenser with a refrigerant-to-fluid condenser inside the CRAC casing, subsection 9. Liquid coolant consisting of water mixed with ethylene glycol is circulated between the condenser and a dry cooler (coil with a fan) by a pump package.
Some advantages of this system are:
Candidate for 30 kW to 1000 kW, and where distance exceeds ?? metres. Systems can either be:
The Water-cooled DX is similar to the glycol-cooled version, except that a water loop is used instead of a glycol loop. The dry cooler is replaced with a cooling tower, often on the facility’s roof, where jets of water are cooled by spraying them into a moving air stream.
It is more efficient that Glycol-based systems in hot dry climates, where evaporation in the cooling tower assists with its operation. However, the water treatment must be carefully considered. There is also a strong risk of legionella in these systems if not properly looked after.
Water cooled DX is rarely installed in a unitary fashion. One or more shared cooling towers servicing multiple CRACs with cooled water is by far the most common configuration.
Cooling towers are often operated by facilities management or by the landlord in larger buildings, and water is supplied metered or unmetered “as a service”. The same towers often serve not only technical cooling, but also comfort cooling, process cooling and refrigerated storage (for food and other products) systems.
Chilled water cooling systems involve the supply of chilled water to Computer Room Air Handlers (CRAH) in the data centre environment. CRAHs are similar to CRACs in appearance, and are available in the same wide range of airflow configurations. They are simpler than CRACs, containing only a blower fan, finned water coil and controls.
The chilled water is produced in a separate chiller. The chiller rejects heat from the chilled water loop to the atmosphere in similar ways to DX CRACs. Air-cooled, glycol-cooled and water cooled chillers are all very common.
Although section 13 depicts a unitary system, chilled water systems are almost always installed such that a large number of CRACs or other cooling loads are served by a small number of chillers and cooling towers / fluid coolers. Chilled water systems also can incorporate large buffer tanks for load balancing, energy price optimisation and to provide ride through in case of power failure.
Many buildings, particularly city skyscrapers, use centralised water-cooled chilled water system. A small number of very large cooling towers serve a number of chillers which supply chilled water for data centre, comfort cooling and other cooling purposes. These are generally managed by facilities personnel.
In a multi-tenant building, the landlord will often supply chilled water as a metered chargeable service to tenants. Condenser loop water is often also available at a much cheaper unit rate (which can be used for a DX water-cooled CRAC or local water-cooled chiller for IT purposes).
Generally, we total up the IT loads and pad the result by 30%.
The coefficient of performance indicates how many kW of heat is removed per kW of electrical power input to the air conditioning system. It is calculated as:
The COP has no units since the numerator and denominator have the same units.
Heat is a form of energy, the SI unit of which is the Joule, J. When a given amount of energy is transferred per second (e.g. 1 J s−1), it is given the unit of the Watt, W.
Many ideas around refrigeration and air conditioning originated from the United States, where imperial units are still common. In the imperial system, energy is measured in the British Thermal Unit, or BTU. Power is measured in BTU h−1.
To convert from kW to BTU h−1, we use the relation:
The EER is normally calculated as:
The EER has units of BTU h−1 W−1, but the unit is often omitted.
Note that the EER and COP are directly related by the factor:
The power usage effectiveness () of a data centre environment is:
The is a dimensionless number. An ideal would be 1.
Tony Evans. The different technologies for cooling data centers. White Paper 59, APC Schneider Electric, 2012. URL https://www.apc.com/whitepaper/?wp=59.
Tony Evans. Fundamental principles of air conditioners for information technology. White Paper 57, APC Schneider Electric, 2014. URL https://www.apc.com/whitepaper/?wp=57.
Neil Rasmussen and Brian Standley. Cooling strategies for it wiring closets and small rooms. White Paper 68, APC Schneider Electric, 2020. URL https://www.apc.com/whitepaper/?wp=68.